Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

WYOMISSING HEALTH AND REHABILITATION CENTER

READING, PA · 103 certified beds · Last Life Safety survey August 28, 2025

CMS Certification Number 395237 · first certified May 1968

Ownership

Independently operated (no chain recorded by CMS) · For profit - Limited Liability company

  • Ownership changed October 30, 2019 (change of ownership)from NSL WYOMISSING LLC
10
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
1
Tags cited more than once
Across separate surveys
5
Inspection & testing records
Of the citations on file

Position within PA

10 citations — more than 47% of the 656 certified nursing homes in PA. Compared within PA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 4 citations; the earlier surveys in the window averaged 3. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (July 2026 to August 2026), and past the point by which nine in ten PA facilities have been surveyed. This facility’s last Life Safety survey was August 2025. Facilities in PA are typically surveyed 10–12 months after the last one (median 11), measured over 1,113 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about WYOMISSING HEALTH AND REHABILITATION CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 10 Life Safety citations above. The Physical Environment Index

  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in PA, and nationally. Surveyors differ markedly between states, so the PA figure is the meaningful one.

This facility10PA median10National median11
Citations on file over three years, compared
MeasureCitations
This facility10
Median facility in PA10
Median facility nationally11

Survey history

Citations at each Life Safety survey
32023-0932024-1042025-08
Citations at each Life Safety survey
Survey dateCitations
September 28, 20233
October 24, 20243
August 28, 20254

Most-cited tags

Most-cited tags at this facility
K-03632K-03531K-03551K-02111K-02251K-01611K-05111K-09121
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0363Install corridor and hallway doors that block smoke.22025-08-28
K-0353Inspect, test, and maintain automatic sprinkler systems.12025-08-28
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.12023-09-28
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.12024-10-24
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.12025-08-28
K-0161Use approved construction type or materials.12023-09-28
K-0511Have properly installed electrical wiring and gas equipment.12025-08-28
K-0912Have power receptacles that are properly grounded.12023-09-28

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 4
  • Egress Deficiencies 2
  • Gas, Vacuum, and Electrical Systems Deficiencies 1
  • Construction Deficiencies 1
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies4
Egress Deficiencies2
Gas, Vacuum, and Electrical Systems Deficiencies1
Construction Deficiencies1
Services Deficiencies1
Miscellaneous Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

August 28, 2025 — 4 citations

Citations issued on August 28, 2025
TagWhat the surveyor checksStatus
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (September 30, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 30, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 30, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (September 30, 2025)

October 24, 2024 — 3 citations

Citations issued on October 24, 2024
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (November 11, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (November 11, 2024)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (November 11, 2024)

September 28, 2023 — 3 citations

Citations issued on September 28, 2023
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (October 30, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 30, 2023)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (October 30, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.