Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
EDENBROOK OF YEADON
YEADON, PA · 190 certified beds · Last Life Safety survey April 23, 2026
CMS Certification Number 395374 · first certified August 1977
Ownership
Operated by EDEN SENIOR CARE · For profit - Limited Liability company
- New ownershipOwnership changed February 1, 2025 (change of ownership)from YEADON OPERATIONS LLC
Position within PA
67 citations — more than 100% of the 656 certified nursing homes in PA. Compared within PA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 14 citations; the earlier surveys in the window averaged 26.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens March 2027 — about 5 months from now. This facility’s last Life Safety survey was April 2026. Facilities in PA are typically surveyed 10–12 months after the last one (median 11), measured over 1,113 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about EDENBROOK OF YEADON
One email when it happens. No account; stop it any time with one click.
8 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
15 of the 67 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
13 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 67 Life Safety citations above. The Physical Environment Index
- F-0880 Provide and implement an infection prevention and control program.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
How that compares
Compared with the median facility in PA, and nationally. Surveyors differ markedly between states, so the PA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 67 |
| Median facility in PA | 10 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| July 3, 2024 | 33 |
| May 1, 2025 | 20 |
| April 23, 2026 | 14 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | 3 | 2026-04-23 |
| K-0324 | Provide properly protected cooking facilities. | 3 | 2026-04-23 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 3 | 2026-04-23 |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | 3 | 2026-04-23 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 3 | 2026-04-23 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2026-04-23 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2026-04-23 |
| K-0342 | Have a complete alarm system manually initiated and initiated by fire sprinkler system connection. | 2 | 2026-04-23 |
What the citations cover
- Smoke Deficiencies 22
- Emergency Preparedness Deficiencies 15
- Egress Deficiencies 11
- Gas, Vacuum, and Electrical Systems Deficiencies 9
- Other 10
| Category | Citations |
|---|---|
| Smoke Deficiencies | 22 |
| Emergency Preparedness Deficiencies | 15 |
| Egress Deficiencies | 11 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 9 |
| Construction Deficiencies | 4 |
| Services Deficiencies | 3 |
| Miscellaneous Deficiencies | 3 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
April 23, 2026 — 14 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0342 | Have a complete alarm system manually initiated and initiated by fire sprinkler system connection. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0346 | Follow proper procedures when the fire alarm was out of service for more than 4 hours. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (June 19, 2026) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 19, 2026) |
May 1, 2025 — 20 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0131 | Meet requirements for sections of health care facilities separated by fire resistive construction. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 12, 2025) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (June 12, 2025) |
July 3, 2024 — 33 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (August 14, 2024) |
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (August 14, 2024) |
| E-0007 | Address patient/client population and determine types of services needed. | Deficient, Provider has date of correction (August 14, 2024) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (August 14, 2024) |
| E-0018 | Establish procedures for tracking staff and patients during an emergency. | Deficient, Provider has date of correction (August 14, 2024) |
| E-0022 | Establish policies and procedures for sheltering. | Deficient, Provider has date of correction (August 14, 2024) |
| E-0023 | Establish policies and procedures for medical documentation. | Deficient, Provider has date of correction (August 14, 2024) |
| E-0024 | Establish policies and procedures for volunteers. | Deficient, Provider has date of correction (August 14, 2024) |
| E-0025 | Create arrangements with other facilities to receive patients. | Deficient, Provider has date of correction (August 14, 2024) |
| E-0026 | Establish roles under a Waiver declared by secretary. | Deficient, Provider has date of correction (August 14, 2024) |
| E-0029 | Develop a communication plan. | Deficient, Provider has date of correction (August 14, 2024) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (August 14, 2024) |
| E-0032 | Provide primary/alternate means for communication. | Deficient, Provider has date of correction (August 14, 2024) |
| E-0035 | Provide family notifications of emergency plan. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0131 | Meet requirements for sections of health care facilities separated by fire resistive construction. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0342 | Have a complete alarm system manually initiated and initiated by fire sprinkler system connection. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0912 | Have power receptacles that are properly grounded. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (August 14, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (August 14, 2024) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.