Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
LAUDERDALE COMMUNITY LIVING CENTER
RIPLEY, TN · 71 certified beds · Last Life Safety survey August 14, 2025
CMS Certification Number 445354 · first certified August 1995
Ownership
Operated by COMMUNITY ELDERCARE SERVICES · For profit - Limited Liability company
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within TN
28 citations — more than 97% of the 303 certified nursing homes in TN. Compared within TN rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 14 citations; the earlier surveys in the window averaged 4.7. With 4 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens November 2026 — about 1 month from now. This facility’s last Life Safety survey was August 2025. Facilities in TN are typically surveyed 15–44 months after the last one (median 33), measured over 279 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about LAUDERDALE COMMUNITY LIVING CENTER
One email when it happens. No account; stop it any time with one click.
3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
8 of the 28 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 28 Life Safety citations above. The Physical Environment Index
How that compares
Compared with the median facility in TN, and nationally. Surveyors differ markedly between states, so the TN figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 28 |
| Median facility in TN | 8 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| March 23, 2023 | 7 |
| June 12, 2024 | 6 |
| April 29, 2025 | 1 |
| August 14, 2025 | 14 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2025-08-14 |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | 2 | 2025-08-14 |
| K-0363 | Install corridor and hallway doors that block smoke. | 2 | 2025-08-14 |
| E-0039 | Conduct testing and exercise requirements. | 2 | 2025-08-14 |
| K-0712 | Have simulated fire drills held at unexpected times. | 2 | 2025-08-14 |
| E-0006 | Conduct risk assessment and an All-Hazards approach. | 1 | 2024-06-12 |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | 1 | 2025-08-14 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 1 | 2025-08-14 |
What the citations cover
- Emergency Preparedness Deficiencies 8
- Smoke Deficiencies 7
- Egress Deficiencies 5
- Miscellaneous Deficiencies 4
- Other 4
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 8 |
| Smoke Deficiencies | 7 |
| Egress Deficiencies | 5 |
| Miscellaneous Deficiencies | 4 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 3 |
| Services Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
August 14, 2025 — 14 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0343 | Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (September 10, 2025) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (September 10, 2025) |
April 29, 2025 — 1 citation
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (June 2, 2025) |
June 12, 2024 — 6 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (June 29, 2024) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (June 29, 2024) |
| E-0025 | Create arrangements with other facilities to receive patients. | Deficient, Provider has date of correction (June 29, 2024) |
| E-0032 | Provide primary/alternate means for communication. | Deficient, Provider has date of correction (June 29, 2024) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (June 29, 2024) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (June 29, 2024) |
March 23, 2023 — 7 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (May 1, 2023) |
| E-0013 | Develop Emergency Preparedness policies and procedures. | Deficient, Provider has date of correction (May 1, 2023) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (May 1, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (May 1, 2023) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (May 1, 2023) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (May 1, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (May 1, 2023) |