Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Viridian Wellness & Rehabilitation

Arlington, TX · 204 certified beds · Last Life Safety survey February 19, 2026

CMS Certification Number 675112 · first certified February 1993

Ownership

Independently operated (no chain recorded by CMS) · For profit - Limited Liability company

  • Ownership changed June 1, 2024 (change of ownership)to CORAL REHABILITATION AND NURSING OF ARLINGTON from 112 GIBBINS RD OPERATIONS LLC
49
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
13
Tags cited more than once
Across separate surveys
21
Inspection & testing records
Of the citations on file

Position within TX

49 citations — more than 100% of the 1,177 certified nursing homes in TX. Compared within TX rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Holding steadyabout the same at the latest survey as at its earlier surveys in the window.

The latest survey found 16 citations; the earlier surveys in the window averaged 16.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens March 2027 — about 6 months from now. This facility’s last Life Safety survey was February 2026. Facilities in TX are typically surveyed 13–14 months after the last one (median 14), measured over 1,905 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Viridian Wellness & Rehabilitation

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

6 of the 49 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

23 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 49 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0926 Have policies on smoking.

How that compares

Citations on file over three years

Compared with the median facility in TX, and nationally. Surveyors differ markedly between states, so the TX figure is the meaningful one.

This facility49TX median7National median11
Citations on file over three years, compared
MeasureCitations
This facility49
Median facility in TX7
Median facility nationally11

Survey history

Citations at each Life Safety survey
192024-11142025-09162026-02
Citations at each Life Safety survey
Survey dateCitations
November 19, 202419
September 16, 202514
February 19, 202616

Most-cited tags

Most-cited tags at this facility
K-03533K-07613K-03633K-03213K-02222K-03242K-09182K-01612
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-02-19
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.32026-02-19
K-0363Install corridor and hallway doors that block smoke.32026-02-19
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32026-02-19
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22025-09-16
K-0324Provide properly protected cooking facilities.22025-09-16
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-09-16
K-0161Use approved construction type or materials.22026-02-19

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 21
  • Egress Deficiencies 8
  • Miscellaneous Deficiencies 7
  • Emergency Preparedness Deficiencies 6
  • Other 7
Citations by CMS category
CategoryCitations
Smoke Deficiencies21
Egress Deficiencies8
Miscellaneous Deficiencies7
Emergency Preparedness Deficiencies6
Construction Deficiencies3
Gas, Vacuum, and Electrical Systems Deficiencies3
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 19, 2026 — 16 citations

Citations issued on February 19, 2026
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (April 5, 2026)
E-0009Include a process for Emergency Preparedness collaboration.Deficient, Provider has date of correction (April 5, 2026)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (April 5, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (April 5, 2026)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (April 5, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (April 5, 2026)
K-0342Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.Deficient, Provider has date of correction (April 5, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 5, 2026)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (April 5, 2026)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (April 5, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 5, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (April 5, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (April 5, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 5, 2026)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (April 5, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (April 5, 2026)

September 16, 2025 — 14 citations

Citations issued on September 16, 2025
TagWhat the surveyor checksStatus
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (October 28, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (October 28, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (October 28, 2025)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (October 28, 2025)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (October 28, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (October 28, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 28, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 28, 2025)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (October 30, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 28, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 28, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (October 28, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 28, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 30, 2025)

November 19, 2024 — 19 citations

Citations issued on November 19, 2024
TagWhat the surveyor checksStatus
E-0001Establish an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (December 16, 2024)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (December 16, 2024)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (December 16, 2024)
K-0133Install a two-hour-resistant firewall separation.Deficient, Provider has date of correction (December 16, 2024)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (December 16, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (December 16, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (December 16, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (December 16, 2024)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (December 16, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (December 16, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 16, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (December 16, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 16, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (December 16, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (December 16, 2024)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (December 16, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (December 16, 2024)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (December 16, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 16, 2024)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.