24
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
2
Tags cited more than once
Across separate surveys
9
Inspection & testing records
Of the citations on file

Position within TX

24 citations — more than 97% of the 1,177 certified nursing homes in TX. Compared within TX rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 4 citations; the earlier surveys in the window averaged 10. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens September 2026. This facility’s last Life Safety survey was August 2025. Facilities in TX are typically surveyed 13–14 months after the last one (median 14), measured over 1,905 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Cityview Nursing and Rehabilitation Center

One email when it happens. No account; stop it any time with one click.

Which alerts

1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

8 of the 24 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 24 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.

How that compares

Citations on file over three years

Compared with the median facility in TX, and nationally. Surveyors differ markedly between states, so the TX figure is the meaningful one.

This facility24TX median7National median11
Citations on file over three years, compared
MeasureCitations
This facility24
Median facility in TX7
Median facility nationally11

Survey history

Citations at each Life Safety survey
02023-06202024-0742025-08
Citations at each Life Safety survey
Survey dateCitations
June 8, 20230
July 25, 202420
August 21, 20254

Most-cited tags

Most-cited tags at this facility
K-05112E-00092E-00301K-07121K-02811K-03461E-00061E-00371
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0511Have properly installed electrical wiring and gas equipment.22025-08-21
E-0009Include a process for Emergency Preparedness collaboration.22025-08-21
E-0030List the names and contact information of those in the facility.12025-08-21
K-0712Have simulated fire drills held at unexpected times.12024-07-25
K-0281Install proper backup exit lighting.12024-07-25
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.12024-07-25
E-0006Conduct risk assessment and an All-Hazards approach.12024-07-25
E-0037Establish staff and initial training requirements.12024-07-25

What the citations cover

Citations by CMS category
  • Emergency Preparedness Deficiencies 8
  • Smoke Deficiencies 7
  • Egress Deficiencies 4
  • Miscellaneous Deficiencies 2
  • Other 3
Citations by CMS category
CategoryCitations
Emergency Preparedness Deficiencies8
Smoke Deficiencies7
Egress Deficiencies4
Miscellaneous Deficiencies2
Services Deficiencies2
Gas, Vacuum, and Electrical Systems Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

August 21, 2025 — 4 citations

Citations issued on August 21, 2025
TagWhat the surveyor checksStatus
E-0009Include a process for Emergency Preparedness collaboration.Deficient, Provider has date of correction (August 22, 2025)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (August 22, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 22, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 22, 2025)

July 25, 2024 — 20 citations

Citations issued on July 25, 2024
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (August 23, 2024)
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (August 23, 2024)
E-0009Include a process for Emergency Preparedness collaboration.Deficient, Provider has date of correction (August 23, 2024)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (August 23, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (August 23, 2024)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (August 23, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (August 23, 2024)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (August 23, 2024)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (August 23, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 23, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 23, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 23, 2024)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (August 23, 2024)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (August 23, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 23, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 23, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 23, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 23, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (August 23, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 23, 2024)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.