Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
FAIRMONT CROSSING HEALTH AND REHAB CENTER
AMHERST, VA · 120 certified beds · Last Life Safety survey March 5, 2026
CMS Certification Number 495363 · first certified July 2002
Ownership
Operated by HILL VALLEY HEALTHCARE · For profit - Corporation
- Ownership changed November 1, 2021 (change of ownership)from CENTRA HEALTH, INC
Position within VA
31 citations — more than 97% of the 289 certified nursing homes in VA. Compared within VA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 16 citations; the earlier surveys on file averaged 7.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens November 2028 — about 24 months from now. This facility’s last Life Safety survey was March 2026. Facilities in VA are typically surveyed 32–45 months after the last one (median 38), measured over 123 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured
Get an email about FAIRMONT CROSSING HEALTH AND REHAB CENTER
One email when it happens. No account; stop it any time with one click.
Emergency preparedness
10 of the 31 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 31 Life Safety citations above. The Physical Environment Index
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0880 Provide and implement an infection prevention and control program.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0908 Keep all essential equipment working safely.
How that compares
Compared with the median facility in VA, and nationally. Surveyors differ markedly between states, so the VA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 31 |
| Median facility in VA | 10 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| March 4, 2020 | 1 |
| June 2, 2022 | 14 |
| March 5, 2026 | 16 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | 2 | 2026-03-05 |
| K-0324 | Provide properly protected cooking facilities. | 1 | 2020-03-04 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 1 | 2026-03-05 |
| K-0363 | Install corridor and hallway doors that block smoke. | 1 | 2022-06-02 |
| E-0037 | Establish staff and initial training requirements. | 1 | 2026-03-05 |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | 1 | 2022-06-02 |
| K-0711 | Provide a written emergency evacuation plan. | 1 | 2022-06-02 |
| E-0009 | Include a process for Emergency Preparedness collaboration. | 1 | 2026-03-05 |
What the citations cover
- Emergency Preparedness Deficiencies 10
- Smoke Deficiencies 9
- Egress Deficiencies 4
- Gas, Vacuum, and Electrical Systems Deficiencies 3
- Other 5
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 10 |
| Smoke Deficiencies | 9 |
| Egress Deficiencies | 4 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 3 |
| Services Deficiencies | 3 |
| Miscellaneous Deficiencies | 2 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
March 5, 2026 — 16 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0009 | Include a process for Emergency Preparedness collaboration. | Deficient, Provider has date of correction (April 3, 2026) |
| E-0024 | Establish policies and procedures for volunteers. | Deficient, Provider has date of correction (April 8, 2026) |
| E-0029 | Develop a communication plan. | Deficient, Provider has date of correction (April 8, 2026) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (April 8, 2026) |
| E-0031 | Provide emergency officials' contact information. | Deficient, Provider has date of correction (April 8, 2026) |
| E-0032 | Provide primary/alternate means for communication. | Deficient, Provider has date of correction (April 8, 2026) |
| E-0033 | Establish methods for sharing information. | Deficient, Provider has date of correction (April 8, 2026) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (April 8, 2026) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (April 8, 2026) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (April 8, 2026) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (July 28, 2026) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (July 28, 2026) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (July 28, 2026) |
| K-0343 | Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire. | Deficient, Provider has date of correction (July 28, 2026) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (July 28, 2026) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (July 28, 2026) |
June 2, 2022 — 14 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (January 20, 2023) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (January 20, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (January 20, 2023) |
| K-0352 | Properly install and monitor supervisory attachments on automatic sprinkler systems. | Deficient, Provider has date of correction (January 20, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Waiver has been granted (January 20, 2023) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (January 20, 2023) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (August 9, 2022) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (January 20, 2023) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (January 20, 2023) |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | Deficient, Provider has date of correction (August 9, 2022) |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (January 20, 2023) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (January 20, 2023) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (August 9, 2022) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (January 20, 2023) |
March 4, 2020 — 1 citation
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (September 1, 2020) |