Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

AVAMERE REHABILITATION OF ISSAQUAH

ISSAQUAH, WA · 140 certified beds · Last Life Safety survey July 2, 2026

CMS Certification Number 505004 · first certified January 1967

Ownership

Operated by AVAMERE · For profit - Limited Liability company

  • Ownership changed March 1, 2023 (change of ownership)from NORTHWEST CARE-ISSAQUAH INC
45
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
12
Tags cited more than once
Across separate surveys
20
Inspection & testing records
Of the citations on file

Position within WA

45 citations — more than 80% of the 193 certified nursing homes in WA. Compared within WA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 11 citations; the earlier surveys on file averaged 17. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens June 2027 — about 7 months from now. This facility’s last Life Safety survey was July 2026. Facilities in WA are typically surveyed 12–15 months after the last one (median 13), measured over 320 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about AVAMERE REHABILITATION OF ISSAQUAH

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

8 of the 45 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 45 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations in CMS's current file

Compared with the median facility in WA, and nationally. Surveyors differ markedly between states, so the WA figure is the meaningful one.

This facility45WA median31National median11
Citations in CMS's current file, compared
MeasureCitations
This facility45
Median facility in WA31
Median facility nationally11

Survey history

Citations at each Life Safety survey
252024-0292025-03112026-07
Citations at each Life Safety survey
Survey dateCitations
February 6, 202425
March 27, 20259
July 2, 202611

Most-cited tags

Most-cited tags at this facility
K-09202K-03452K-07412K-09212K-09182K-05112K-03532K-07612
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0920Ensure proper usage of power strips and extension cords.22025-03-27
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22025-03-27
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22026-07-02
K-0921Ensure that testing and maintenance of electrical equipment is performed.22025-03-27
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-03-27
K-0511Have properly installed electrical wiring and gas equipment.22026-07-02
K-0353Inspect, test, and maintain automatic sprinkler systems.22026-07-02
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.22026-07-02

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 12
  • Gas, Vacuum, and Electrical Systems Deficiencies 10
  • Emergency Preparedness Deficiencies 8
  • Miscellaneous Deficiencies 7
  • Other 8
Citations by CMS category
CategoryCitations
Smoke Deficiencies12
Gas, Vacuum, and Electrical Systems Deficiencies10
Emergency Preparedness Deficiencies8
Miscellaneous Deficiencies7
Services Deficiencies4
Egress Deficiencies4

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

July 2, 2026 — 11 citations

Citations issued on July 2, 2026
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (July 31, 2026)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 31, 2026)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (July 31, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 31, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 31, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 31, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 31, 2026)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 31, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 9, 2026)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (July 31, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 31, 2026)

March 27, 2025 — 9 citations

Citations issued on March 27, 2025
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (April 25, 2025)
E-0018Establish procedures for tracking staff and patients during an emergency.Deficient, Provider has date of correction (April 25, 2025)
E-0023Establish policies and procedures for medical documentation.Deficient, Provider has date of correction (April 25, 2025)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (April 25, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (April 25, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 25, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 25, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 25, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (April 25, 2025)

February 6, 2024 — 25 citations

Citations issued on February 6, 2024
TagWhat the surveyor checksStatus
E-0034Provide a means of sharing information on occupancy/needs.Deficient, Provider has date of correction (February 22, 2024)
E-0035Provide family notifications of emergency plan.Deficient, Provider has date of correction (February 22, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (February 22, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (February 29, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (February 29, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (February 29, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (February 22, 2024)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (February 22, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (February 29, 2024)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (February 22, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (February 29, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (February 29, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (February 29, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (February 29, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (April 1, 2024)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (February 29, 2024)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (February 22, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (February 29, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (February 22, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (February 29, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (February 29, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 29, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (February 22, 2024)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (February 29, 2024)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (February 29, 2024)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.