Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

AVAMERE REHABILITATION OF ISSAQUAH

ISSAQUAH, WA · 140 certified beds · Last Life Safety survey March 27, 2025

CMS Certification Number 505004 · first certified January 1967

Ownership

Operated by AVAMERE · For profit - Limited Liability company

  • Ownership changed March 1, 2023 (change of ownership)from NORTHWEST CARE-ISSAQUAH INC
35
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
7
Tags cited more than once
Across separate surveys
15
Inspection & testing records
Of the citations on file

Position within WA

35 citations — more than 59% of the 193 certified nursing homes in WA. Compared within WA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 9 citations; the earlier surveys in the window averaged 13. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (March 2026 to June 2026), and past the point by which nine in ten WA facilities have been surveyed. This facility’s last Life Safety survey was March 2025. Facilities in WA are typically surveyed 12–15 months after the last one (median 13), measured over 320 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about AVAMERE REHABILITATION OF ISSAQUAH

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

7 of the 35 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

6 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 35 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in WA, and nationally. Surveyors differ markedly between states, so the WA figure is the meaningful one.

This facility35WA median31National median11
Citations on file over three years, compared
MeasureCitations
This facility35
Median facility in WA31
Median facility nationally11

Survey history

Citations at each Life Safety survey
12022-10252024-0292025-03
Citations at each Life Safety survey
Survey dateCitations
October 12, 20221
February 6, 202425
March 27, 20259

Most-cited tags

Most-cited tags at this facility
K-09202K-03452K-09212E-00392K-09182K-03632K-03242K-09141
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0920Ensure proper usage of power strips and extension cords.22025-03-27
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22025-03-27
K-0921Ensure that testing and maintenance of electrical equipment is performed.22025-03-27
E-0039Conduct testing and exercise requirements.22025-03-27
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-03-27
K-0363Install corridor and hallway doors that block smoke.22024-02-06
K-0324Provide properly protected cooking facilities.22025-03-27
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.12024-02-06

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 11
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Emergency Preparedness Deficiencies 7
  • Miscellaneous Deficiencies 4
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies11
Gas, Vacuum, and Electrical Systems Deficiencies8
Emergency Preparedness Deficiencies7
Miscellaneous Deficiencies4
Services Deficiencies3
Egress Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 27, 2025 — 9 citations

Citations issued on March 27, 2025
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (April 25, 2025)
E-0018Establish procedures for tracking staff and patients during an emergency.Deficient, Provider has date of correction (April 25, 2025)
E-0023Establish policies and procedures for medical documentation.Deficient, Provider has date of correction (April 25, 2025)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (April 25, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (April 25, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 25, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 25, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 25, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (April 25, 2025)

February 6, 2024 — 25 citations

Citations issued on February 6, 2024
TagWhat the surveyor checksStatus
E-0034Provide a means of sharing information on occupancy/needs.Deficient, Provider has date of correction (February 22, 2024)
E-0035Provide family notifications of emergency plan.Deficient, Provider has date of correction (February 22, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (February 22, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (February 29, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (February 29, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (February 29, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (February 22, 2024)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (February 22, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (February 29, 2024)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (February 22, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (February 29, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (February 29, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (February 29, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (February 29, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (April 1, 2024)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (February 29, 2024)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (February 22, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (February 29, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (February 22, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (February 29, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (February 29, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 29, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (February 22, 2024)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (February 29, 2024)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (February 29, 2024)

October 12, 2022 — 1 citation

Citations issued on October 12, 2022
TagWhat the surveyor checksStatus
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 7, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.