Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Alderwood Post Acute & Rehabilitation

LYNNWOOD, WA · 113 certified beds · Last Life Safety survey July 14, 2026

CMS Certification Number 505319 · first certified May 1988

Ownership

Operated by HILL VALLEY HEALTHCARE · For profit - Limited Liability company

  • Ownership changed April 1, 2023 (change of ownership)from MANOR CARE OF LYNNWOOD WA, ASSOCIATION
53
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
13
Tags cited more than once
Across separate surveys
22
Inspection & testing records
Of the citations on file

Position within WA

53 citations — more than 88% of the 193 certified nursing homes in WA. Compared within WA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 30 citations; the earlier surveys on file averaged 11.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens July 2027 — about 8 months from now. This facility’s last Life Safety survey was July 2026. Facilities in WA are typically surveyed 12–15 months after the last one (median 13), measured over 320 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about Alderwood Post Acute & Rehabilitation

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

15 of the 53 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

8 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 53 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.

How that compares

Citations in CMS's current file

Compared with the median facility in WA, and nationally. Surveyors differ markedly between states, so the WA figure is the meaningful one.

This facility53WA median31National median11
Citations in CMS's current file, compared
MeasureCitations
This facility53
Median facility in WA31
Median facility nationally11

Survey history

Citations at each Life Safety survey
112024-11122025-08302026-07
Citations at each Life Safety survey
Survey dateCitations
November 15, 202411
August 20, 202512
July 14, 202630

Most-cited tags

Most-cited tags at this facility
K-03453K-02223K-09183K-03533E-00392K-05212K-07612K-01002
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32026-07-14
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.32026-07-14
K-0918Have generator or other power source capable of supplying service within 10 seconds.32026-07-14
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-07-14
E-0039Conduct testing and exercise requirements.22026-07-14
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.22026-07-14
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.22026-07-14
K-0100Meet other general requirements.22026-07-14

What the citations cover

Citations by CMS category
  • Emergency Preparedness Deficiencies 15
  • Smoke Deficiencies 12
  • Egress Deficiencies 9
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Other 10
Citations by CMS category
CategoryCitations
Emergency Preparedness Deficiencies15
Smoke Deficiencies12
Egress Deficiencies9
Gas, Vacuum, and Electrical Systems Deficiencies7
Miscellaneous Deficiencies5
Services Deficiencies3
Construction Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

July 14, 2026 — 30 citations

Citations issued on July 14, 2026
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (August 13, 2026)
E-0009Include a process for Emergency Preparedness collaboration.Deficient, Provider has date of correction (August 13, 2026)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (August 13, 2026)
E-0018Establish procedures for tracking staff and patients during an emergency.Deficient, Provider has date of correction (August 13, 2026)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (August 13, 2026)
E-0029Develop a communication plan.Deficient, Provider has date of correction (August 13, 2026)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (August 13, 2026)
E-0031Provide emergency officials' contact information.Deficient, Provider has date of correction (August 13, 2026)
E-0033Establish methods for sharing information.Deficient, Provider has date of correction (August 13, 2026)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (August 13, 2026)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (August 13, 2026)
K-0100Meet other general requirements.Deficient, Provider has date of correction (August 13, 2026)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 13, 2026)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 13, 2026)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (August 13, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 13, 2026)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (August 13, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 10, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 10, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (August 13, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 10, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 10, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 13, 2026)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (September 10, 2026)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (September 10, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 10, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 13, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 10, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 13, 2026)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (September 10, 2026)

August 20, 2025 — 12 citations

Citations issued on August 20, 2025
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (September 16, 2025)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (September 16, 2025)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (September 16, 2025)
K-0100Meet other general requirements.Deficient, Provider has date of correction (September 16, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (September 16, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (September 16, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 16, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 16, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 16, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (September 16, 2025)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (September 16, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 10, 2025)

November 15, 2024 — 11 citations

Citations issued on November 15, 2024
TagWhat the surveyor checksStatus
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (December 10, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (December 10, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (December 10, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (December 10, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (December 10, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 10, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (December 10, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (December 10, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (December 10, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 10, 2024)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (December 10, 2024)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.