Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
REDMOND CARE AND REHABILITATION CENTER
REDMOND, WA · 139 certified beds · Last Life Safety survey June 13, 2025
CMS Certification Number 505181 · first certified May 1968
Ownership
Operated by THE ENSIGN GROUP · For profit - Corporation
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within WA
20 citations — more than 24% of the 193 certified nursing homes in WA. Compared within WA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 8 citations; the earlier surveys in the window averaged 6. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Past the typical window (May 2026 to September 2026). Most WA facilities have been surveyed by September 2026. This facility’s last Life Safety survey was June 2025. Facilities in WA are typically surveyed 12–15 months after the last one (median 13), measured over 320 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about REDMOND CARE AND REHABILITATION CENTER
One email when it happens. No account; stop it any time with one click.
4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
4 of the 20 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
3 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 20 Life Safety citations above. The Physical Environment Index
How that compares
Compared with the median facility in WA, and nationally. Surveyors differ markedly between states, so the WA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 20 |
| Median facility in WA | 31 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| May 21, 2023 | 10 |
| June 12, 2024 | 2 |
| June 13, 2025 | 8 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2024-06-12 |
| K-0324 | Provide properly protected cooking facilities. | 2 | 2025-06-13 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 2 | 2025-06-13 |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | 2 | 2025-06-13 |
| K-0511 | Have properly installed electrical wiring and gas equipment. | 2 | 2025-06-13 |
| E-0035 | Provide family notifications of emergency plan. | 1 | 2025-06-13 |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | 1 | 2023-05-21 |
| K-0712 | Have simulated fire drills held at unexpected times. | 1 | 2023-05-21 |
What the citations cover
- Gas, Vacuum, and Electrical Systems Deficiencies 7
- Smoke Deficiencies 6
- Emergency Preparedness Deficiencies 4
- Services Deficiencies 2
- Other 1
| Category | Citations |
|---|---|
| Gas, Vacuum, and Electrical Systems Deficiencies | 7 |
| Smoke Deficiencies | 6 |
| Emergency Preparedness Deficiencies | 4 |
| Services Deficiencies | 2 |
| Miscellaneous Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
June 13, 2025 — 8 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (July 15, 2025) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (July 15, 2025) |
| E-0035 | Provide family notifications of emergency plan. | Deficient, Provider has date of correction (July 15, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (July 15, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (July 15, 2025) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (July 15, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (July 15, 2025) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (July 15, 2025) |
June 12, 2024 — 2 citations
May 21, 2023 — 10 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (June 22, 2023) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (June 22, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Waiver has been granted (June 22, 2023) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (June 22, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (June 22, 2023) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (June 22, 2023) |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | Deficient, Provider has date of correction (June 22, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (June 22, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (June 22, 2023) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (June 22, 2023) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.