Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

RENTON HEALTH & REHABILITATION

RENTON, WA · 99 certified beds · Last Life Safety survey January 13, 2026

CMS Certification Number 505280 · first certified April 1984

Ownership

Operated by VERTICAL HEALTH SERVICES · For profit - Limited Liability company

  • Ownership changed September 1, 2023 (change of ownership)from WA3 OP RENTON LLC
52
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
13
Tags cited more than once
Across separate surveys
17
Inspection & testing records
Of the citations on file

Position within WA

52 citations — more than 86% of the 193 certified nursing homes in WA. Compared within WA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Holding steadyabout the same at the latest survey as at its earlier surveys in the window.

The latest survey found 17 citations; the earlier surveys in the window averaged 17.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens December 2026 — about 3 months from now. This facility’s last Life Safety survey was January 2026. Facilities in WA are typically surveyed 12–15 months after the last one (median 13), measured over 320 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about RENTON HEALTH & REHABILITATION

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

16 of the 52 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

11 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 52 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in WA, and nationally. Surveyors differ markedly between states, so the WA figure is the meaningful one.

This facility52WA median31National median11
Citations on file over three years, compared
MeasureCitations
This facility52
Median facility in WA31
Median facility nationally11

Survey history

Citations at each Life Safety survey
102023-05252024-09172026-01
Citations at each Life Safety survey
Survey dateCitations
May 24, 202310
September 16, 202425
January 13, 202617

Most-cited tags

Most-cited tags at this facility
K-03533K-02933K-07512E-00372K-03742E-00152E-00202K-03242
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-01-13
K-0293Have properly located and lighted "Exit" signs.32026-01-13
K-0751Have restrictions on the use of flammable curtains.22026-01-13
E-0037Establish staff and initial training requirements.22024-09-16
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.22026-01-13
E-0015Address subsistence needs for staff and patients.22026-01-13
E-0020Establish policies and procedures including evacuation.22026-01-13
K-0324Provide properly protected cooking facilities.22026-01-13

What the citations cover

Citations by CMS category
  • Emergency Preparedness Deficiencies 16
  • Smoke Deficiencies 16
  • Egress Deficiencies 9
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Other 5
Citations by CMS category
CategoryCitations
Emergency Preparedness Deficiencies16
Smoke Deficiencies16
Egress Deficiencies9
Gas, Vacuum, and Electrical Systems Deficiencies6
Miscellaneous Deficiencies4
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

January 13, 2026 — 17 citations

Citations issued on January 13, 2026
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (February 25, 2026)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (February 25, 2026)
E-0023Establish policies and procedures for medical documentation.Deficient, Provider has date of correction (February 25, 2026)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (February 25, 2026)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (February 25, 2026)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (February 25, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (February 25, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (February 25, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (February 25, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 26, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (February 25, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (February 25, 2026)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (February 25, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (February 25, 2026)
K-0751Have restrictions on the use of flammable curtains.Deficient, Provider has date of correction (February 25, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 20, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (February 25, 2026)

September 16, 2024 — 25 citations

Citations issued on September 16, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (October 23, 2024)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (October 23, 2024)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (October 23, 2024)
E-0023Establish policies and procedures for medical documentation.Deficient, Provider has date of correction (October 23, 2024)
E-0024Establish policies and procedures for volunteers.Deficient, Provider has date of correction (October 23, 2024)
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (October 23, 2024)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (October 23, 2024)
E-0033Establish methods for sharing information.Deficient, Provider has date of correction (October 23, 2024)
E-0035Provide family notifications of emergency plan.Deficient, Provider has date of correction (October 23, 2024)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (October 23, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (October 23, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (October 23, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (October 23, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 23, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 23, 2024)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (October 23, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 23, 2024)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (October 23, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (October 23, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (October 23, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 23, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 23, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 23, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (October 23, 2024)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (October 23, 2024)

May 24, 2023 — 10 citations

Citations issued on May 24, 2023
TagWhat the surveyor checksStatus
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (June 9, 2023)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (June 9, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (June 9, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (June 9, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (June 9, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (June 9, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 9, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (June 9, 2023)
K-0751Have restrictions on the use of flammable curtains.Deficient, Provider has date of correction (June 9, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 9, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.