Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
FIRCREST NURSING FACILITY
SEATTLE, WA · 110 certified beds · Last Life Safety survey November 7, 2025
CMS Certification Number 50A260 · first certified May 1994
Ownership
Independently operated (no chain recorded by CMS) · Government - State
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within WA
52 citations — more than 86% of the 193 certified nursing homes in WA. Compared within WA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 16 citations; the earlier surveys in the window averaged 18. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens October 2026 — about 1 month from now. This facility’s last Life Safety survey was November 2025. Facilities in WA are typically surveyed 12–15 months after the last one (median 13), measured over 320 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about FIRCREST NURSING FACILITY
One email when it happens. No account; stop it any time with one click.
4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
16 of the 52 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
6 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 52 Life Safety citations above. The Physical Environment Index
How that compares
Compared with the median facility in WA, and nationally. Surveyors differ markedly between states, so the WA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 52 |
| Median facility in WA | 31 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| August 7, 2023 | 25 |
| November 7, 2024 | 11 |
| November 7, 2025 | 16 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2025-11-07 |
| K-0920 | Ensure proper usage of power strips and extension cords. | 3 | 2025-11-07 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2025-11-07 |
| E-0039 | Conduct testing and exercise requirements. | 2 | 2025-11-07 |
| E-0036 | Establish emergency prep training and testing. | 2 | 2025-11-07 |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | 2 | 2025-11-07 |
| K-0511 | Have properly installed electrical wiring and gas equipment. | 2 | 2024-11-07 |
| K-0781 | Have restrictions on the use of portable space heaters. | 2 | 2025-11-07 |
What the citations cover
- Emergency Preparedness Deficiencies 16
- Smoke Deficiencies 12
- Gas, Vacuum, and Electrical Systems Deficiencies 11
- Miscellaneous Deficiencies 5
- Other 8
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 16 |
| Smoke Deficiencies | 12 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 11 |
| Miscellaneous Deficiencies | 5 |
| Egress Deficiencies | 4 |
| Services Deficiencies | 2 |
| Construction Deficiencies | 2 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
November 7, 2025 — 16 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (November 30, 2025) |
| E-0009 | Include a process for Emergency Preparedness collaboration. | Deficient, Provider has date of correction (November 30, 2025) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (November 30, 2025) |
| E-0024 | Establish policies and procedures for volunteers. | Deficient, Provider has date of correction (November 30, 2025) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (November 30, 2025) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (November 30, 2025) |
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (December 8, 2025) |
| K-0346 | Follow proper procedures when the fire alarm was out of service for more than 4 hours. | Deficient, Provider has date of correction (November 30, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (December 8, 2025) |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | Deficient, Provider has date of correction (November 30, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (December 8, 2025) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (December 8, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (November 30, 2025) |
| K-0781 | Have restrictions on the use of portable space heaters. | Deficient, Provider has date of correction (November 30, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (December 8, 2025) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (November 30, 2025) |
November 7, 2024 — 11 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (December 5, 2024) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (December 5, 2024) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (December 5, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (December 5, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (December 5, 2024) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (December 5, 2024) |
| K-0915 | Have proper power supply for life support equipment. | Deficient, Provider has date of correction (December 5, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (December 5, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (December 5, 2024) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (December 5, 2024) |
| K-0926 | Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk. | Deficient, Provider has date of correction (December 5, 2024) |
August 7, 2023 — 25 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (September 7, 2023) |
| E-0018 | Establish procedures for tracking staff and patients during an emergency. | Deficient, Provider has date of correction (September 7, 2023) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (October 6, 2023) |
| E-0023 | Establish policies and procedures for medical documentation. | Deficient, Provider has date of correction (September 7, 2023) |
| E-0033 | Establish methods for sharing information. | Deficient, Provider has date of correction (September 7, 2023) |
| E-0034 | Provide a means of sharing information on occupancy/needs. | Deficient, Provider has date of correction (September 7, 2023) |
| E-0035 | Provide family notifications of emergency plan. | Deficient, Provider has date of correction (September 7, 2023) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (September 7, 2023) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0351 | Install an approved automatic sprinkler system. | Waiver has been granted (September 7, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Waiver has been granted (September 7, 2023) |
| K-0781 | Have restrictions on the use of portable space heaters. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (September 7, 2023) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (September 7, 2023) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.