Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Transitional Care Of Seattle

SEATTLE, WA · 165 certified beds · Last Life Safety survey September 23, 2025

CMS Certification Number 505534 · first certified December 2020

Ownership

Operated by EVERGREEN HEALTHCARE GROUP · For profit - Limited Liability company

  • Ownership changed August 31, 2023 (change of ownership)to TRANSITIONAL CARE CENTER OF SEATTLE from EMPRES AT SEATTLE LLC
29
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
5
Tags cited more than once
Across separate surveys
8
Inspection & testing records
Of the citations on file

Position within WA

29 citations — more than 45% of the 193 certified nursing homes in WA. Compared within WA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 16 citations; the earlier surveys in the window averaged 6.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: September 2026 to December 2026. This facility’s last Life Safety survey was September 2025. Facilities in WA are typically surveyed 12–15 months after the last one (median 13), measured over 320 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Transitional Care Of Seattle

One email when it happens. No account; stop it any time with one click.

Which alerts

3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

3 of the 29 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 29 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in WA, and nationally. Surveyors differ markedly between states, so the WA figure is the meaningful one.

This facility29WA median31National median11
Citations on file over three years, compared
MeasureCitations
This facility29
Median facility in WA31
Median facility nationally11

Survey history

Citations at each Life Safety survey
112023-0322024-06162025-09
Citations at each Life Safety survey
Survey dateCitations
March 2, 202311
June 13, 20242
September 23, 202516

Most-cited tags

Most-cited tags at this facility
K-09203K-07122K-02222K-03532K-09182K-03741K-03241K-09261
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0920Ensure proper usage of power strips and extension cords.32025-09-23
K-0712Have simulated fire drills held at unexpected times.22025-09-23
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22025-09-23
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-09-23
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-09-23
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.12025-09-23
K-0324Provide properly protected cooking facilities.12025-09-23
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.12023-03-02

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 8
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Egress Deficiencies 5
  • Emergency Preparedness Deficiencies 3
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies8
Gas, Vacuum, and Electrical Systems Deficiencies8
Egress Deficiencies5
Emergency Preparedness Deficiencies3
Miscellaneous Deficiencies3
Services Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

September 23, 2025 — 16 citations

Citations issued on September 23, 2025
TagWhat the surveyor checksStatus
E-0009Include a process for Emergency Preparedness collaboration.Deficient, Provider has date of correction (October 20, 2025)
E-0034Provide a means of sharing information on occupancy/needs.Deficient, Provider has date of correction (October 20, 2025)
K-0100Meet other general requirements.Deficient, Provider has date of correction (October 20, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (October 20, 2025)
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (October 20, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 20, 2025)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (October 20, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 20, 2025)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (October 20, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (October 20, 2025)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (October 20, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 20, 2025)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (October 20, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 20, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (October 20, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (October 20, 2025)

June 13, 2024 — 2 citations

Citations issued on June 13, 2024
TagWhat the surveyor checksStatus
E-0032Provide primary/alternate means for communication.Deficient, Provider has date of correction (August 1, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 1, 2024)

March 2, 2023 — 11 citations

Citations issued on March 2, 2023
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (April 9, 2023)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (April 9, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (April 9, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (April 9, 2023)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (April 9, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 9, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (April 9, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 9, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 9, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 9, 2023)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (April 9, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.