Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
WASHINGTON CARE CENTER
SEATTLE, WA · 165 certified beds · Last Life Safety survey December 16, 2025
CMS Certification Number 505017 · first certified July 1978
Ownership
Independently operated (no chain recorded by CMS) · For profit - Limited Liability company
- Ownership changed April 1, 2020 (change of ownership)from WASHINGTON CARE SERVICES
Position within WA
65 citations — more than 95% of the 193 certified nursing homes in WA. Compared within WA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 17 citations; the earlier surveys in the window averaged 24. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens December 2026 — about 2 months from now. This facility’s last Life Safety survey was December 2025. Facilities in WA are typically surveyed 12–15 months after the last one (median 13), measured over 320 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about WASHINGTON CARE CENTER
One email when it happens. No account; stop it any time with one click.
9 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
19 of the 65 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
13 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 65 Life Safety citations above. The Physical Environment Index
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0880 Provide and implement an infection prevention and control program.
- F-0909 Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
How that compares
Compared with the median facility in WA, and nationally. Surveyors differ markedly between states, so the WA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 65 |
| Median facility in WA | 31 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| June 14, 2023 | 30 |
| August 21, 2024 | 18 |
| December 16, 2025 | 17 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| E-0009 | Include a process for Emergency Preparedness collaboration. | 3 | 2025-12-16 |
| K-0920 | Ensure proper usage of power strips and extension cords. | 3 | 2025-12-16 |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | 3 | 2025-12-16 |
| K-0324 | Provide properly protected cooking facilities. | 2 | 2025-12-16 |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | 2 | 2024-08-21 |
| K-0511 | Have properly installed electrical wiring and gas equipment. | 2 | 2024-08-21 |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | 2 | 2024-08-21 |
| K-0712 | Have simulated fire drills held at unexpected times. | 2 | 2025-12-16 |
What the citations cover
- Emergency Preparedness Deficiencies 19
- Smoke Deficiencies 14
- Gas, Vacuum, and Electrical Systems Deficiencies 10
- Egress Deficiencies 9
- Other 13
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 19 |
| Smoke Deficiencies | 14 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 10 |
| Egress Deficiencies | 9 |
| Services Deficiencies | 7 |
| Miscellaneous Deficiencies | 5 |
| Construction Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
December 16, 2025 — 17 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0009 | Include a process for Emergency Preparedness collaboration. | Deficient, Provider has date of correction (January 15, 2026) |
| E-0033 | Establish methods for sharing information. | Deficient, Provider has date of correction (January 15, 2026) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (January 15, 2026) |
August 21, 2024 — 18 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0009 | Include a process for Emergency Preparedness collaboration. | Deficient, Provider has date of correction (September 6, 2024) |
| E-0013 | Develop Emergency Preparedness policies and procedures. | Deficient, Provider has date of correction (September 20, 2024) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (September 23, 2024) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (September 20, 2024) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (September 20, 2024) |
| E-0031 | Provide emergency officials' contact information. | Deficient, Provider has date of correction (August 28, 2024) |
| E-0033 | Establish methods for sharing information. | Deficient, Provider has date of correction (September 23, 2024) |
| E-0034 | Provide a means of sharing information on occupancy/needs. | Deficient, Provider has date of correction (September 20, 2024) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (October 10, 2024) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (September 6, 2024) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (September 6, 2024) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (September 6, 2024) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (September 6, 2024) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (October 18, 2024) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (September 6, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (September 6, 2024) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (October 18, 2024) |
| K-0926 | Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk. | Deficient, Provider has date of correction (September 20, 2024) |
June 14, 2023 — 30 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (July 19, 2023) |
| E-0009 | Include a process for Emergency Preparedness collaboration. | Deficient, Provider has date of correction (July 19, 2023) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (July 19, 2023) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (July 19, 2023) |
| E-0032 | Provide primary/alternate means for communication. | Deficient, Provider has date of correction (July 19, 2023) |
| E-0034 | Provide a means of sharing information on occupancy/needs. | Deficient, Provider has date of correction (July 19, 2023) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (July 19, 2023) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0324 | Provide properly protected cooking facilities. | Waiver has been granted (July 19, 2023) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Waiver has been granted (July 19, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Waiver has been granted (July 19, 2023) |
| K-0525 | Enure that solid fuel-burning fireplaces are not in patient sleeping areas. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Waiver has been granted (July 19, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (July 19, 2023) |
| K-0926 | Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk. | Deficient, Provider has date of correction (July 19, 2023) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.