Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
AVAMERE TRANSITIONAL CARE OF PUGET SOUND
TACOMA, WA · 60 certified beds · Last Life Safety survey November 25, 2025
CMS Certification Number 505529 · first certified March 2017
Ownership
Operated by AVAMERE · For profit - Limited Liability company
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within WA
50 citations — more than 85% of the 193 certified nursing homes in WA. Compared within WA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 21 citations; the earlier surveys in the window averaged 14.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens November 2026 — about 1 month from now. This facility’s last Life Safety survey was November 2025. Facilities in WA are typically surveyed 12–15 months after the last one (median 13), measured over 320 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about AVAMERE TRANSITIONAL CARE OF PUGET SOUND
One email when it happens. No account; stop it any time with one click.
5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
23 of the 50 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 50 Life Safety citations above. The Physical Environment Index
How that compares
Compared with the median facility in WA, and nationally. Surveyors differ markedly between states, so the WA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 50 |
| Median facility in WA | 31 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| August 18, 2023 | 17 |
| July 31, 2024 | 12 |
| November 25, 2025 | 21 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0712 | Have simulated fire drills held at unexpected times. | 3 | 2025-11-25 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2025-11-25 |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | 3 | 2025-11-25 |
| E-0037 | Establish staff and initial training requirements. | 3 | 2025-11-25 |
| K-0363 | Install corridor and hallway doors that block smoke. | 2 | 2025-11-25 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 2 | 2024-07-31 |
| K-0511 | Have properly installed electrical wiring and gas equipment. | 2 | 2025-11-25 |
| E-0015 | Address subsistence needs for staff and patients. | 2 | 2025-11-25 |
What the citations cover
- Emergency Preparedness Deficiencies 23
- Smoke Deficiencies 12
- Gas, Vacuum, and Electrical Systems Deficiencies 6
- Miscellaneous Deficiencies 4
- Other 5
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 23 |
| Smoke Deficiencies | 12 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 6 |
| Miscellaneous Deficiencies | 4 |
| Services Deficiencies | 3 |
| Egress Deficiencies | 2 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
November 25, 2025 — 21 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (October 24, 2025) |
| E-0007 | Address patient/client population and determine types of services needed. | Deficient, Provider has date of correction (October 24, 2025) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (October 24, 2025) |
| E-0018 | Establish procedures for tracking staff and patients during an emergency. | Deficient, Provider has date of correction (October 24, 2025) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (October 24, 2025) |
| E-0022 | Establish policies and procedures for sheltering. | Deficient, Provider has date of correction (October 24, 2025) |
| E-0033 | Establish methods for sharing information. | Deficient, Provider has date of correction (October 24, 2025) |
| E-0034 | Provide a means of sharing information on occupancy/needs. | Deficient, Provider has date of correction (October 24, 2025) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (October 24, 2025) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (November 25, 2025) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (October 24, 2025) |
| K-0232 | Have corridors or aisles that are unobstructed and are at least 8 feet in width. | Deficient, Provider has date of correction (October 24, 2025) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (October 24, 2025) |
| K-0346 | Follow proper procedures when the fire alarm was out of service for more than 4 hours. | Deficient, Provider has date of correction (October 24, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (October 24, 2025) |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | Deficient, Provider has date of correction (October 24, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (October 24, 2025) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (October 24, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (October 24, 2025) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (October 24, 2025) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (November 25, 2025) |
July 31, 2024 — 12 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (August 26, 2024) |
| E-0023 | Establish policies and procedures for medical documentation. | Deficient, Provider has date of correction (August 26, 2024) |
| E-0032 | Provide primary/alternate means for communication. | Deficient, Provider has date of correction (August 26, 2024) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (August 26, 2024) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (August 26, 2024) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (August 26, 2024) |
August 18, 2023 — 17 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0001 | Establish an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (September 19, 2023) |
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (September 19, 2023) |
| E-0013 | Develop Emergency Preparedness policies and procedures. | Deficient, Provider has date of correction (September 19, 2023) |
| E-0026 | Establish roles under a Waiver declared by secretary. | Deficient, Provider has date of correction (September 19, 2023) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (September 19, 2023) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (September 19, 2023) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (October 11, 2023) |
| K-0324 | Provide properly protected cooking facilities. | Waiver has been granted (October 11, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (October 13, 2023) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (September 19, 2023) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (October 11, 2023) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (September 19, 2023) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (October 13, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (October 11, 2023) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (October 11, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (October 11, 2023) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (October 11, 2023) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.