Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Bayshore Nursing & Rehab

GLENDALE, WI · 112 certified beds · Last Life Safety survey September 30, 2025

CMS Certification Number 525371 · first certified October 1984

Ownership

Operated by BEDROCK HEALTHCARE · For profit - Limited Liability company

  • Ownership changed October 1, 2019 (change of ownership)to SILVER SPRINGS HEALTH CARE CENTER from DYCORA TRANSITIONAL HEALTH-GLENDALE LLC
51
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
16
Tags cited more than once
Across separate surveys
24
Inspection & testing records
Of the citations on file

Position within WI

51 citations — more than 100% of the 323 certified nursing homes in WI. Compared within WI rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 20 citations; the earlier surveys in the window averaged 15.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens November 2026 — about 1 month from now. This facility’s last Life Safety survey was September 2025. Facilities in WI are typically surveyed 13–15 months after the last one (median 14), measured over 516 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Bayshore Nursing & Rehab

One email when it happens. No account; stop it any time with one click.

Which alerts

8 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

3 of the 51 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

23 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 51 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
  • F-0908 Keep all essential equipment working safely.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.

How that compares

Citations on file over three years

Compared with the median facility in WI, and nationally. Surveyors differ markedly between states, so the WI figure is the meaningful one.

This facility51WI median17National median11
Citations on file over three years, compared
MeasureCitations
This facility51
Median facility in WI17
Median facility nationally11

Survey history

Citations at each Life Safety survey
152023-03162024-06202025-09
Citations at each Life Safety survey
Survey dateCitations
March 21, 202315
June 20, 202416
September 30, 202520

Most-cited tags

Most-cited tags at this facility
K-03533K-03453K-03213K-07123K-03243K-02713K-09183K-02912
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-09-30
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-09-30
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32025-09-30
K-0712Have simulated fire drills held at unexpected times.32025-09-30
K-0324Provide properly protected cooking facilities.32025-09-30
K-0271Have exits that are accessible at all times.32025-09-30
K-0918Have generator or other power source capable of supplying service within 10 seconds.32025-09-30
K-0291Install emergency lighting that can last at least 1 1/2 hours.22025-09-30

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 18
  • Egress Deficiencies 11
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Miscellaneous Deficiencies 7
  • Other 7
Citations by CMS category
CategoryCitations
Smoke Deficiencies18
Egress Deficiencies11
Gas, Vacuum, and Electrical Systems Deficiencies8
Miscellaneous Deficiencies7
Services Deficiencies4
Emergency Preparedness Deficiencies3

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

September 30, 2025 — 20 citations

Citations issued on September 30, 2025
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (December 15, 2025)
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (January 5, 2026)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (December 15, 2025)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (December 15, 2025)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (December 15, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (December 15, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (December 15, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (December 15, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (December 15, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 15, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (December 15, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 15, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has plan of correction
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (December 15, 2025)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (December 15, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (December 15, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (December 15, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (December 30, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 15, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (December 15, 2025)

June 20, 2024 — 16 citations

Citations issued on June 20, 2024
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 19, 2024)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (June 18, 2024)
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (July 25, 2024)
K-0233Install resident room doors of proper design and width.Deficient, Provider has date of correction (July 25, 2024)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (August 19, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 19, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 19, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 19, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 19, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 25, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 19, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (August 19, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (August 19, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 21, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 19, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 19, 2024)

March 21, 2023 — 15 citations

Citations issued on March 21, 2023
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (April 19, 2023)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (April 19, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (April 19, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (April 19, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (April 19, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 19, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 19, 2023)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (April 19, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 19, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (April 19, 2023)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (April 19, 2023)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (April 19, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 19, 2023)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (April 19, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 19, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.