Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

DOVE HEALTHCARE - LODI

LODI, WI · 50 certified beds · Last Life Safety survey February 18, 2026

CMS Certification Number 525520 · first certified December 1992

Ownership

Operated by DOVE HEALTHCARE · For profit - Corporation

  • Ownership changed February 15, 2019 (change of ownership)to DIVINE REHABILITATION AND NURSING AT LODI LLC from THE EVANGELICAL LUTHERAN GOOD SAMARITAN SOCIETY
39
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
10
Tags cited more than once
Across separate surveys
19
Inspection & testing records
Of the citations on file

Position within WI

39 citations — more than 96% of the 323 certified nursing homes in WI. Compared within WI rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 6 citations; the earlier surveys in the window averaged 16.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens March 2027 — about 6 months from now. This facility’s last Life Safety survey was February 2026. Facilities in WI are typically surveyed 13–15 months after the last one (median 14), measured over 516 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about DOVE HEALTHCARE - LODI

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

6 of the 39 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

3 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 39 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in WI, and nationally. Surveyors differ markedly between states, so the WI figure is the meaningful one.

This facility39WI median17National median11
Citations on file over three years, compared
MeasureCitations
This facility39
Median facility in WI17
Median facility nationally11

Survey history

Citations at each Life Safety survey
142023-08192024-0962026-02
Citations at each Life Safety survey
Survey dateCitations
August 29, 202314
September 27, 202419
February 18, 20266

Most-cited tags

Most-cited tags at this facility
K-03723K-03533K-03242K-09142K-07122K-03452K-09182K-07112
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.32026-02-18
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-02-18
K-0324Provide properly protected cooking facilities.22026-02-18
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22024-09-27
K-0712Have simulated fire drills held at unexpected times.22024-09-27
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22024-09-27
K-0918Have generator or other power source capable of supplying service within 10 seconds.22024-09-27
K-0711Provide a written emergency evacuation plan.22026-02-18

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 20
  • Emergency Preparedness Deficiencies 6
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Miscellaneous Deficiencies 4
  • Other 3
Citations by CMS category
CategoryCitations
Smoke Deficiencies20
Emergency Preparedness Deficiencies6
Gas, Vacuum, and Electrical Systems Deficiencies6
Miscellaneous Deficiencies4
Services Deficiencies2
Egress Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 18, 2026 — 6 citations

Citations issued on February 18, 2026
TagWhat the surveyor checksStatus
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 18, 2026)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (March 18, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 18, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (March 18, 2026)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (March 18, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (March 18, 2026)

September 27, 2024 — 19 citations

Citations issued on September 27, 2024
TagWhat the surveyor checksStatus
E-0013Develop Emergency Preparedness policies and procedures.Deficient, Provider has date of correction (October 26, 2024)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (October 26, 2024)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (October 26, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (October 17, 2024)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (October 17, 2024)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (October 17, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 17, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 17, 2024)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (October 17, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Past Non-Compliance (October 17, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Past Non-Compliance (October 17, 2024)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (October 17, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Past Non-Compliance (October 17, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Past Non-Compliance (October 17, 2024)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (October 17, 2024)
K-0712Have simulated fire drills held at unexpected times.Past Non-Compliance (October 17, 2024)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (October 17, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Past Non-Compliance (October 17, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Past Non-Compliance (October 17, 2024)

August 29, 2023 — 14 citations

Citations issued on August 29, 2023
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (September 25, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (September 25, 2023)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (September 25, 2023)
K-0331Construct fire resistant interior walls.Deficient, Provider has date of correction (September 25, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 25, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 25, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 25, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 25, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 25, 2023)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (September 25, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Waiver has been granted (December 20, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 25, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (September 25, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 25, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.