Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
Heritage Health Services
Port Washington, WI · 50 certified beds · Last Life Safety survey March 12, 2025
CMS Certification Number 525586 · first certified June 1996
Ownership
Operated by NORTH SHORE HEALTHCARE · For profit - Limited Liability company
- Ownership changed October 1, 2017 (change of ownership)from FMG NORTH WISCONSIN STREET WISCONSIN LLC
Position within WI
41 citations — more than 98% of the 323 certified nursing homes in WI. Compared within WI rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 12 citations; the earlier surveys in the window averaged 14.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Well past the typical window (April 2026 to June 2026), and past the point by which nine in ten WI facilities have been surveyed. This facility’s last Life Safety survey was March 2025. Facilities in WI are typically surveyed 13–15 months after the last one (median 14), measured over 516 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about Heritage Health Services
One email when it happens. No account; stop it any time with one click.
5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
6 of the 41 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 41 Life Safety citations above. The Physical Environment Index
How that compares
Compared with the median facility in WI, and nationally. Surveyors differ markedly between states, so the WI figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 41 |
| Median facility in WI | 17 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| January 26, 2023 | 10 |
| February 6, 2024 | 19 |
| March 12, 2025 | 12 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0712 | Have simulated fire drills held at unexpected times. | 3 | 2025-03-12 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 3 | 2025-03-12 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 2 | 2025-03-12 |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | 2 | 2025-03-12 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2025-03-12 |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | 2 | 2025-03-12 |
| K-0919 | Meet requirements for the use of electrical equipment. | 2 | 2024-02-06 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 2 | 2024-02-06 |
What the citations cover
- Smoke Deficiencies 14
- Gas, Vacuum, and Electrical Systems Deficiencies 8
- Emergency Preparedness Deficiencies 6
- Egress Deficiencies 5
- Other 8
| Category | Citations |
|---|---|
| Smoke Deficiencies | 14 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 8 |
| Emergency Preparedness Deficiencies | 6 |
| Egress Deficiencies | 5 |
| Services Deficiencies | 3 |
| Miscellaneous Deficiencies | 3 |
| Construction Deficiencies | 2 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
March 12, 2025 — 12 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (April 11, 2025) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (April 11, 2025) |
| K-0133 | Install a two-hour-resistant firewall separation. | Deficient, Provider has date of correction (April 11, 2025) |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (April 11, 2025) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (April 11, 2025) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Deficient, Provider has date of correction (April 11, 2025) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (April 11, 2025) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (April 11, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (April 11, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (April 11, 2025) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (April 30, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (April 11, 2025) |
February 6, 2024 — 19 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0013 | Develop Emergency Preparedness policies and procedures. | Deficient, Provider has date of correction (March 4, 2024) |
| E-0025 | Create arrangements with other facilities to receive patients. | Deficient, Provider has date of correction (March 4, 2024) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (March 4, 2024) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (March 4, 2024) |
January 26, 2023 — 10 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (March 10, 2023) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (March 10, 2023) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (March 10, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (March 10, 2023) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (March 10, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (March 10, 2023) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (March 10, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (March 10, 2023) |
| K-0919 | Meet requirements for the use of electrical equipment. | Deficient, Provider has date of correction (March 10, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (March 10, 2023) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.