Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

St. John's Health Care Corporation

Rochester, NY · 455 certified beds · Last Life Safety survey June 9, 2025

CMS Certification Number 335008 · first certified June 1972

Also on this campus

The same campus holds a state-licensed assisted living facility, with its own state record on the Assisted Living Index: The Hawthorne (1 Johnsarbor Dr W). Matched by the telephone number the two records share. The records are separate and are never added together.

Ownership

Independently operated (no chain recorded by CMS) · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

14
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
3
Tags cited more than once
Across separate surveys
8
Inspection & testing records
Of the citations on file

Position within NY

14 citations — more than 50% of the 592 certified nursing homes in NY. Compared within NY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 2 citations; the earlier surveys on file averaged 6. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens November 2026 — about 1 month from now. This facility’s last Life Safety survey was June 2025. Facilities in NY are typically surveyed 18–25 months after the last one (median 21), measured over 520 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about St. John's Health Care Corporation

One email when it happens. No account; stop it any time with one click.

Which alerts

3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

3 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 14 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations in CMS's current file

Compared with the median facility in NY, and nationally. Surveyors differ markedly between states, so the NY figure is the meaningful one.

This facility14NY median14National median11
Citations in CMS's current file, compared
MeasureCitations
This facility14
Median facility in NY14
Median facility nationally11

Survey history

Citations at each Life Safety survey
42021-1182023-1222025-06
Citations at each Life Safety survey
Survey dateCitations
November 8, 20214
December 13, 20238
June 9, 20252

Most-cited tags

Most-cited tags at this facility
K-03722K-03452K-09182K-02321K-02221K-03211K-05411K-09211
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22023-12-13
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22023-12-13
K-0918Have generator or other power source capable of supplying service within 10 seconds.22023-12-13
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.12021-11-08
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.12025-06-09
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.12023-12-13
K-0541Install properly constructed and protected linen or trash chutes.12023-12-13
K-0921Ensure that testing and maintenance of electrical equipment is performed.12023-12-13

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 6
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Egress Deficiencies 2
  • Services Deficiencies 1
Citations by CMS category
CategoryCitations
Smoke Deficiencies6
Gas, Vacuum, and Electrical Systems Deficiencies5
Egress Deficiencies2
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 9, 2025 — 2 citations

Citations issued on June 9, 2025
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 8, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 5, 2025)

December 13, 2023 — 8 citations

Citations issued on December 13, 2023
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (February 11, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (February 11, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (February 11, 2024)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (February 11, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 11, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (February 11, 2024)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (February 11, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (February 11, 2024)

November 8, 2021 — 4 citations

Citations issued on November 8, 2021
TagWhat the surveyor checksStatus
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (January 21, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 21, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (January 21, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 21, 2022)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.